Backflow happens when water flows the wrong way, from a building's plumbing back into the public drinking water system. It can be caused by back pressure from boilers, pumps and process equipment, or by back siphonage when pressure drops in the city main during a water main break or fire-fighting. A backflow preventer is a testable valve assembly that stops contaminated water from entering the supply.
POM Plumbing installs, repairs and replaces backflow prevention devices across Toronto and the GTA, from residential dual checks to large RP assemblies in commercial and industrial buildings. We handle device selection, permits, cross-connection surveys, testing and the paperwork the City requires. For annual inspections, see our backflow testing service.
Under the City of Toronto Water Supply By-law (Municipal Code Chapter 851), industrial, commercial and institutional properties and larger multi-residential buildings must have premise isolation backflow prevention installed right after the water meter and its bypass. Some homes also need protection where there is a cross-connection.
| Property | Typical requirement |
|---|---|
| Industrial, commercial, institutional | Premise isolation, annual testing |
| Condos and apartment buildings (Part 3) | Premise isolation, annual testing |
| Restaurants and food service | DCVA or RP depending on hazard |
| Medical, labs, auto shops, chemical use | RP assembly (severe hazard) |
| Fire sprinkler systems | DCDA or RP on fire line |
| Homes with irrigation, boilers or pools | Zone or fixture protection |
The right device depends on the hazard level at your connection. We select and size it to CSA B64.10 and the By-law.
| Device | Hazard | Typical use |
|---|---|---|
| RP / RPZ (reduced pressure principle) | Severe | Medical, labs, chemical, auto, car washes |
| DCVA (double check valve assembly) | Moderate | Offices, retail, restaurants, condos |
| DCDA (double check detector) | Moderate | Fire sprinkler lines |
| PVB (pressure vacuum breaker) | Zone | Lawn irrigation |
| Dual check / AVB | Minor | Individual fixtures and homes |
New premise and zone devices installed with isolation valves, drains and clearances for testing.
A site survey identifies every hazard and recommends the protection the City requires.
Checks, springs, seals and relief valves rebuilt when a device fails its test.
Old or obsolete assemblies replaced, often during a planned water shut-down.
Plumbing permits and drawings where required, and coordination with your engineer.
From survey to sign-off, we manage the full installation so your building stays compliant.
These two are often confused. A backflow preventer protects the clean drinking water supply from contamination. A backwater valve is installed on the sewer line and stops sewage from flowing back into your basement during heavy rain. Homes usually need a backwater valve; most commercial and multi-unit buildings need a backflow preventer. We install both.

Installed prices depend on device type, pipe size, access and whether a shut-down or permit is needed. Typical Toronto ranges:
| Service | Typical cost |
|---|---|
| Residential dual check or PVB | $400 – $900 |
| DCVA installation (3/4" – 2") | $1,200 – $3,500 |
| RP installation (3/4" – 2") | $1,800 – $4,500 |
| Large assemblies (3" and up) | quoted after survey |
| Rebuild of a failed device | $250 – $650 |
| Cross-connection survey | $300 – $800 |
Most single-family homes do not need a testable backflow preventer, but protection is required where there is a cross-connection: lawn irrigation systems, hydronic boilers, pool fill lines, water treatment equipment or a fire sprinkler system. We install dual checks, vacuum breakers or a testable device as required, and test it where the By-law calls for it.

Under the By-law, devices must be tested when installed, after any repair or service, and at least once a year. Failing to install or test can lead to City orders, fines or interruption of water service.
Need help with a City notice? Call (905) 625-8777. See also commercial plumbing and condo plumbing.
With our company, you can be assured that we are fully licensed and insured to work on your plumbing and sanitation systems, providing you with the peace of mind you deserve.
We stand behind our work and offer the best warranty in the market. This means that you can be confident in our repairs, and if anything goes wrong, we'll be there to make it right.
We have over 20 years of experience in the plumbing industry, which means that we have seen it all. Our knowledge and expertise allow us to provide top-notch service to our clients every time.
We understand that plumbing repairs can be costly, which is why we offer affordable pricing without sacrificing the quality of our work. When you choose us, you can get the repairs you need at a price you can afford.
A backflow preventer is a valve assembly that stops water from flowing back from your building into the city water supply. It is required for most commercial, industrial, institutional and multi-residential buildings in Toronto, and for homes with certain cross-connections.
Most single-family homes do not need a testable device. Protection is required where there is a cross-connection, such as lawn irrigation, a hydronic boiler, pool fill or water treatment equipment.
A DCVA uses two check valves and is used for moderate hazards such as offices and restaurants. An RP adds a relief valve between the checks and is required for severe hazards such as labs, medical offices and auto shops.
Residential devices typically cost $400 to $900. DCVA installations usually cost $1,200 to $3,500 and RP installations $1,800 to $4,500 for common sizes. Large assemblies are quoted after a survey.
The City of Toronto Water Supply By-law, Municipal Code Chapter 851, requires premise isolation backflow prevention for industrial, commercial, institutional and larger multi-residential properties.
At installation, after any repair or service, and at least once a year. See our backflow testing page for details.
Often, yes. Many devices can be rebuilt with new checks, seals and springs. If the body is damaged or parts are unavailable, we replace the assembly and retest it.
No. A backflow preventer protects drinking water. A backwater valve protects your basement from sewer backup. We install both.
Yes. Fire lines usually need a double check detector assembly or an RP, depending on the system and additives.
Installation must be done by a licensed plumber, and testing by a certified backflow tester. Our team handles both.