A pressure reducing valve (PRV) lowers incoming water pressure to a safe, steady level. In Toronto, street pressure can exceed 80 psi, and in high-rise buildings booster pumps push water even higher so it reaches the top floors. Without working PRVs, the lower floors of each pressure zone would see pressure high enough to burst supply lines, damage fixtures and cause water hammer. The Ontario Building Code limits static pressure at fixtures to about 80 psi (550 kPa), and most homes and suites work best at 50 to 70 psi.
POM Plumbing inspects, services, rebuilds and replaces PRVs in condos, apartment buildings, commercial properties and houses across Toronto and the GTA. We record inlet and outlet pressures, clean strainers, rebuild or replace valves, add bypasses where needed and leave a documented baseline for your maintenance records.
Water hammer when taps close, often on the lower floors of a zone.
Strong pressure at night and weak pressure at peak morning use.
Toilet fill valves and relief valves that keep running or dripping.
Failed braided hoses, dishwasher and washing machine lines in several suites.
Low pressure at the top of a zone because the valve is sticking closed.
Outlet pressure far from the set point or creeping up with no flow.
PRV problems show up differently depending on the building and system.
| Building | Typical PRV setup | Common issues |
|---|---|---|
| Detached house | One PRV after the water meter | High pressure, leaking fixtures, water hammer |
| Townhouse / low-rise | PRV per building or block | Pressure creep, failed strainers |
| High-rise condo | PRV stations per pressure zone | Swings between floors, failed diaphragms |
| Commercial building | PRVs on domestic and process lines | Equipment damage, noise |
A building PRV replacement is planned around residents, usually as a one-day event.
Many PRVs can be rebuilt with new diaphragms, seats and strainers, which is usually the best option for valves under about 10 years old in good condition. Replacement is recommended when the body is corroded, parts are discontinued, the valve no longer holds a steady pressure after a rebuild, or the station lacks isolation valves and a bypass. Most PRVs last 10 to 15 years.

Budget ranges for Toronto buildings and homes, before tax. Final prices depend on valve size, access and shut-down requirements.
| Service | Typical cost |
|---|---|
| Residential PRV replacement | $450 – $900 |
| Building PRV inspection and testing | $600 – $2,000 |
| PRV service or rebuild | $1,500 – $4,000 |
| Small to medium building PRV replacement | $3,500 – $9,000 |
| Large or complex PRV station | $10,000 – $20,000+ |
| Task | Frequency |
|---|---|
| Pressure check on each zone | Every 6 to 12 months |
| Strainer cleaning | Annually |
| Full inspection and report | Annually, ideally in the fall |
| Rebuild | Every 3 to 5 years or as needed |
| Replacement | About every 10 to 15 years |
Deferring PRV work rarely saves money. A failed PRV can over-pressurise a whole zone, causing burst supply lines, flooded suites, insurance claims and emergency shut-downs that cost far more than planned maintenance.
With our company, you can be assured that we are fully licensed and insured to work on your plumbing and sanitation systems, providing you with the peace of mind you deserve.
We stand behind our work and offer the best warranty in the market. This means that you can be confident in our repairs, and if anything goes wrong, we'll be there to make it right.
We have over 20 years of experience in the plumbing industry, which means that we have seen it all. Our knowledge and expertise allow us to provide top-notch service to our clients every time.
We understand that plumbing repairs can be costly, which is why we offer affordable pricing without sacrificing the quality of our work. When you choose us, you can get the repairs you need at a price you can afford.
A PRV lowers incoming water pressure to a safe, steady level to protect pipes, fixtures and appliances. Buildings use several PRVs to create pressure zones on different floors.
At least once a year, with pressure checks every 6 to 12 months. Fall is a good time, before winter and before the next capital planning cycle.
Banging pipes, pressure swings, running toilets and relief valves, burst supply lines and gauge readings far from the set point.
Most homes and suites work best at 50 to 70 psi. The Ontario Building Code limits static pressure at fixtures to about 80 psi.
Most PRVs last 10 to 15 years. Rebuilds every few years can extend their life.
Yes. A PRV that fails open lets full street or booster pump pressure into the system, which can burst supply lines and damage fixtures.
Most building PRV replacements take about one day of work, planned as a short shut-down for the affected zone.
Routine inspection and rebuilds are usually operating costs, while full replacement of PRV stations is often planned in the reserve fund. Your reserve fund study and engineer can confirm.
Yes. Booster pump problems, closed or failing isolation valves, clogged strainers and scaled piping can all cause low pressure. We test the whole system.
A residential PRV typically costs $450 to $900 installed. Building PRV replacements usually range from $3,500 to $9,000, and large stations more.
Yes. We install and replace PRVs in houses where street pressure is too high or the existing valve has failed.